DEFINITIONS FOR ILLUMINATED LCD INDICATORS
Line mode
UPS Status Display Capacity
Display
Digital Value Display Select SW
Press
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Batt.
Initial V X -- X V X V
1st V X -- X V X V
2nd V X -- X V X V
3rd V X -- X X V V
4th V X -- X V X V
5th(Return) V X -- X V X V
Press >3sec
(Sound
Disable)
V X V X -- -- -- -- -- -- --
Press >3sec
again(Sound
Enable)
V X X X -- -- -- -- -- -- --
(Overload) V X -- V -- -- -- -- -- -- --
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
Battery mode
UPS Status Display Capacity
Display
Digital Value Display Select SW
Press
Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Batt.
Initial X V -- X V X V
1st X V -- X V X V
2nd X V -- X V X V
3rd X V -- X X V V
4th X V -- X V X V
5th(Return) X V -- X V X V
Press >3sec
(Sound
Disable)
X V V X -- -- -- -- -- -- --
Press >3sec
again(Sound
Enable)
X V X X -- -- -- -- -- -- --
(Overload) X V -- V -- -- -- -- -- -- --
"V" : Illuminated, "X" : Not Illuminated, "--" : Either
TROUBLE SHOOTING
Problem Possible Cause Solution
Full-time surge
protection outlets
stop providing
power to
equipment.
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one
piece of equipment. Wait 10 seconds,
reset the circuit breaker by depressing the
button, and then turn the UPS on.
Battery not fully charged.
Recharge the battery by leaving the UPS
plugged in.
The UPS does
not provide
expected
runtime.
Battery is slightly worn out.
Contact CyberPower Systems about
replacement batteries at
The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.
Turn the UPS off. Wait 10 seconds and
then turn the UPS on.
The battery is worn out.
Contact CyberPower Systems about
replacement batteries at
The UPS will not
turn on.
Mechanical problem.
Contact CyberPower Systems at
The USB cable is not
connected.
Connect the USB cable to the UPS unit
and an open USB port on the back of the
computer.
PowerPanel
®
Business Edition
is inactive.
The unit is not providing
battery power.
Shutdown your computer and turn the
UPS off. Wait 10 seconds and turn the
UPS on. This should reset the unit.
Additional troubleshooting information can be found at eu.cyberpowersystems.com
TECHNICAL SPECIFICATIONS
Model OR1000ELCDRM1U OR1500ELCDRM1U
Capacity (VA) 1000VA/600W 1500VA/900W
Input
Input Voltage Range 160VAC~270VAC
Frequency Range 50/60Hz (Auto Sensing)
AVR Function Boost Only
Output
On Battery Output
Voltage
230Vac +/-10%
On Battery Output
Frequency
50/60Hz +/-1%
Transfer Time 4ms Typical
Overload Protection On Utility: Circuit Breaker, On Battery: Internal Current Limiting
Surge Protection
Lightning / Surge
Protection
Yes
Network/ Phone/ Fax/
Modem Protection
RJ11/RJ45 ( One In/ One Out )
Operating Temperature +32°F to 104°F ( 0°C to 40°C )
Physical
Total # of UPS outlets IEC320 C 13 x 6 ( Backup x 4 )
Maximum
Dimensions(cm)
1U Rack 43.3 x 38.9 x 4.4 1U Rack 43.3 x 48.5 x 4.4
Weight (kg) 16.1 19.4
Battery
Sealed Maintenance
Free Lead Acid Battery
6V / 7Ah x4 6V / 9Ah x4
Typical Recharge Time 8 hours
Charging Current(Max.) 1A
User Replaceable Yes
Status Indicators
Indicators Power On, Wiring Fault, LCD Display
Audible Alarms On Battery, Low Battery, Overload
Communication
PowerPanel
®
Business
Edition Software
Windows 2000/NT/XP/Vista,Mac OSX,Linux
Management
Self -Test Yes
Auto-Charger Yes
Auto-Restart Yes
USB interface Yes
Dry contact Closure Yes
SNMP/HTTP
Networking
Optional
CYBERPOWER GREENPOWER UPS TECHNOLOGY
Our new UPS circuit is designed to save energy operating in GreenPower
Bypass Mode.
A traditional UPS circuit with AVR provides normal output voltage through the
Relay and AVR transformer. The current travels first through the transformer
conducting energy and generating heat. This heat creates energy dissipation
resulting in a "Power Loss" or consumption of utility power and money.
CyberPower's GreenPower Circuit Design is a solution to this "Power Loss." When the Utility Power is
operating normally, our Green Power UPS works in Bypass Mode. Our GreenPower design conducts
power only through the Relay and still provides normal output voltage. Bypassing the transformer
reduces power consumption thereby conserving energy and saving money. When the utility power is
abnormal the UPS will operate under Battery or AVR Mode. Under this condition Green Power UPS and
a traditional UPS would operate about the same.
On average utility power operates 88% of the time and the CyberPower GreenPower Technology will
work in its money/energy saving Bypass Mode.
For more information, visit eu.cyberpowersystems.com
or contact
CyberPower Systems B.V.
Flight Forum 3545 5657DW Eindhoven The Netherlands
Tel: +31 40 2348170, E-MAIL: [email protected]
CyberPower Systems Inc. (USA) 4241 12th Avenue East, Suite 400, Shakopee, MN 55379, U.S.A.
Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: [email protected]
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole
or in part without permission is prohibited. PowerPanel
®
and PowerPanel
®
Plus are trademarks of
CyberPower Systems (USA) Inc.
4. Remove the retaining screw o
f
the cable connectors.
5. Replace the new battery pack. Assemble
the screws, cover, cable and front panel in
the reverse sequence of above steps.
Recharge the unit for 4-8 hours to ensure
the UPS performs expected runtime