Copyright © 2011 CyberPower Systems, Inc.
*)200V are derated by 20%, 208 V are derated by 10% for OL6000RT3U
Yes, ECO Mode Efficiency > 95%
200, 208, 220, 230, 240Vac (Configurable) ±2%
50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz
Transfer Time (Typically)
THD < 3% at Linear Load, < 5% at Non-linear Load
ECO Mode Voltage Regulation
±10%, ±15% (Configurable)
(3) L6-30R, (1) Terminal block
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Line Mode: 105~125% Load for 1 min, 126~150% Load for 10 sec
Battery Mode: 105~130% Load for 10 sec, 131~150% Load for 2 sec
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Recharge Time (Typically)
Multi-Function LCD Readout that Supports:
Multi-Language Interface, (19) Types of Read Out,
(20) Types of Function Setting, (3) Event Logs
Power On (White), Line Mode (Green), Battery Mode (Yellow),
Bypass Mode (Yellow), Fault (Red), Replace Battery (Red)
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery
Operating Relative Humidity
Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
(1) Serial Port (RS232), (1) USB Port, (1) Remote Control Port, (1) Relay Out
(1) Expansion Port (With optional SNMP card or RMCARD 302)
Power Management Software
PowerPanel
®
Business Edition
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Dimensions--Battery Module
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Net Weight--Battery Module